You are using an outdated browser. For a faster, safer browsing experience, upgrade for free today.

BOSCH REXROTH
R911170789


$87.96
  • BOSCH REXROTH
  • Material:R911170789
  • Model:R-IBIL24PWRIN-PAC

Quantity in stock: 0

***Disclaimer: The following summary contains information gathered from various sources such as product descriptions, technical specifications and catalogs. While efforts have been made to provide accurate details, inaccuracies may occur. It is advised to verify all information by contacting Bosch Rexroth directly.***
The Bosch Rexroth R-IB IL 24 PWR IN-PAC (R911170789) is a specialized module designed to integrate seamlessly into an Inline station, providing essential power supply functionality for automation systems. This particular module is engineered to feed the necessary 24V supply voltage into the main circuit UM, ensuring that all connected components receive the power they need for optimal operation. In addition to its primary function, the R-IB IL 24 PWR IN-PAC also offers the capability to supply power for a separate 24V segment circuit US from the same module. This dual functionality makes it a versatile component in any system that requires reliable and efficient distribution of power within its configuration. The compact design and robust construction of this Bosch Rexroth module ensure it can be easily integrated into existing setups, while its precise engineering guarantees consistent performance and longevity in demanding industrial environments.


Inline connector

The modular, compact equipment configuration of the I/O systems from Rexroth offers you maximum flexibility for the cost-effective implementation of your individual machine concepts. The I/O modules have robust design and mechanics, are easy to use, have a quick reaction time and are quick to install – both in the control cabinet and in the field. Open communication standards allow you perfect integration of the I/O modules with maximum availability.

Unpacked Weight: 0.082 kg

This module is designed for use within an Inline station. It enables the 24 V supply voltage to be fed into the main circuit (UM). Power for a 24 V segment circuit (US) can also be provided at this module.

Air pressure (operation)70-106 kPa (up to 3,000 m above sea level)
Air pressure (storage / transport)70-106 kPa (up to 3,000 m above sea level)
Rated value; 24V periphery (main circuit UM)24 V DC
Width12.2
Productgroup ID4,6
Height120
Maximum current8
International protection codeIP20
Permissible air humidity (storage)10-95
Permissible air humidity (transport)10-95
Connection typeZugfederanschluss
Depth71.5
Weight0.082
Ambient temperature (during operation)-25-55
Ambient temperature (storage and transport)-25-85
Conductor cross-sectionRigid: 0.08-0.5 mm²,Flexible: 0.08-0.5 mm²,AWG: 28 ... 16

General data

Type

R-IB IL 24 PWR IN-PAC

Weight 1)

g

59

Ambient temperature (operation)

-25 °C ... +55 °C

Ambient temperature (storage/transport)

-25 °C ... +85 °C

Permissible relative humidity (operation)

10 % ... 95 %, EN 61131-2

Permissible relative humidity (storage/transport)

10 % ... 95 %, EN 61131-2

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20, IEC 60529

Protection class

III, EN 61131-2, IEC 61131-2
1) Including plug

Connection data

Type

R-IB IL 24 PWR IN-PAC

Designation

Inline connection plug

Connection type

Tension spring modules

Conductor cross-section solid/flexible/AWG

0.08 mm² ... 1.5 mm²
0.08 mm² ... 1.5 mm²
28 ... 16

Interface local bus

Type

R-IB IL 24 PWR IN-PAC

Transmission speed 1)

kBit/s

MBit/s

500
2
1) Can be used with this transmission speed in Inline stations, if required

24 V peripheral supply (main circuit UM)

Type

R-IB IL 24 PWR IN-PAC

Connection

+24 V

Terminal points 1.2 and 2.2

Ground (GND)

Terminal points 1.3 and 2.3

Rated value

V DC

24

Tolerance

-15 %/+20 %

Alternating current component

%

5

Permissible range

19.2 V ... 30 V

Maximum permitted power

A

8

Requirement for the voltage supply

If an electrically-isolated area is to be set up, you must supply the feed module from a new mains device. Use an external fuse for the 24 V area.

Overload/short-circuit protection in the segment circuit

No

Overvoltage protection

Yes; suppressor diode for voltage limitation between terminal points 1.1 and 1.3 as well as between terminal points 1.2 and 1.3

Reverse polarity protection

Yes, parallel polarity protection diode

Electrical isolation/insulation of the voltage ranges

Type

R-IB IL 24 PWR IN-PAC

Common potentials

24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area.

Separate potentials in the system of bus coupler/feed module and I/O module

Test distance

Test voltage

5 V supply incoming remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

5 V supply to further remote bus/7.5 V supply (bus logic)

500 V AC, 50 Hz, 1 min.

7.5 V supply (bus logic)/24 V supply (peripherals)

500 V AC, 50 Hz, 1 min.

24 V supply (peripherals)/function earth

500 V AC, 50 Hz, 1 min.

Error messages to the higher-level control or computer system

Type

R-IB IL 24 PWR IN-PAC

Error message

None

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911170789-Inline connector

Dimensions

Type

R-IB IL 24 PWR IN-PAC

A

mm

12.2

B

mm

120

C

mm

71.5

Note on dimensions

The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715).