  • Material:R911173120
  • Model:S20-AI6-AO2-SSI2

Quantity in stock: 2



Cabinet I/O S20

The modular, compact device design of the I/O systems from Rexroth provides you with maximum flexibility for cost-effective implementation of your custom machine concepts. The I/O modules have a robust design and mechanics, Forced ventilated - Axial fan 230Vre easy to handle, have a fast reaction time and are quick to install – both in the control cabinet as well as in the field. Open communication standards allow you to perfectly integrate the I/O modules with maximum availability.

Unpacked Weight: 0.247 kg

This module is designed for use within an S20 station. The module is used to acquire analog input signals and to output analog signals. The SSI interfaces are used to acquire the data from absolute encoders with a resolution between 8 bits and 31 bits and transmission rates up to 4 MHz.

Innovative assembly and installation concept
Individually combinable modules
Space-saving I/O technology for top hat rail mounting
Compact, modular and simple
Type code extensionS20-AI6-AO2-SSI2
Productgroup ID4,6
ctrlX configuratorhttps://www.boschrexroth.com/ctrlx-configurator/
Number of channels2
EPLANhttps://ecad-configuration.boschrexroth.com/?rootpartnr=BOS.S20-AI6-AO2-SSI2**&downloads=true
Weight0.247

General data

Type

S20-AI6-AO2-SSI2

Color

Gray

Weight

g

205

Ambient temperature (operation)

-25 °C ... +60 °C

Ambient temperature (storage/transport)

-40 °C ... +85 °C

Permissible relative humidity (operation)

5 % ... 95 % acc. to DIN EN 61131-2, no dewing

Permissible relative humidity (storage/transport)

5 % ... 95 % acc. to DIN EN 61131-2, no dewing

Air pressure (operation)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Air pressure (storage/transport)

70 kPa ... 106 kPa (up to 3000 m above sea level)

Protection type

IP20

Protection class

III, IEC 61140, EN 61140, VDE 0140-1

Connection data

Type

S20-AI6-AO2-SSI2

Designation

S20 connector

Connection type

Spring-cage connection with direct plug technology

Conductor cross-section solid/flexible/AWG

0.2 mm² ... 1.5 mm²
0.2 mm² ... 1.5 mm²
24 ... 16

Stripping length

mm

8

Permissible cable length

m

≤ 30

Interface local bus

Type

S20-AI6-AO2-SSI2

Connection type

Bus base module

Number

2

Transmission speed

MBit/s

100

Power supply to logic

Type

S20-AI6-AO2-SSI2

Logic voltage UBus 1)

V DC

5

Typical current consumption from UBus

mA

250

Maximum current consumption from UBus

mA

300

Typical power consumption from UBus

W

1.25

Maximum power consumption from UBus

W

1.5
1) Via bus base module

Power supply to peripherals

Type

S20-AI6-AO2-SSI2

Maximum permitted voltage range 1)

​19.2 V DC ... ​30 V DC

Overvoltage/reverse polarity protection supply voltage

Diode (in the L path)

Transient protection

Suppressor diode
1) Including all tolerances, including ripple

Encoder supply

Type

S20-AI6-AO2-SSI2

24 V encoder supply

Short-circuit protection

Electronic, per channel

Transient protection

Suppressor diode

Mechanical tests

Type

S20-AI6-AO2-SSI2

Vibration resistance 1)

g

5

Shock 2)

30 g, 11 ms duration, semi-sinusoidal shock pulse

Continuous shock 3)

g

10
1) Acc. to IEC 60068-2-6
2) Acc. to IEC 60068-2-27
3) Acc. to EN 60068-2-27

Conformity

Type

S20-AI6-AO2-SSI2

Conforms with

Testing of interference immunity acc. to EN 61000-6-2

Discharge of static electricity (ESD)

Criterion B; 6 kV contact discharge; 8 kV air discharge acc. to EN 61000-4-2/IEC 61000-4-2

Electro-magnetic fields

Criterion A; field strength: 10 V/m acc. to EN 61000-4-3/IEC 61000-4-3

Fast transients (burst)

Criterion B; 2 kV acc. to EN 61000-4-4/IEC 61000-4-4

Transient overvoltage (surge)

Criterion B; supply lines DC: ±0.5 kV/±0.5 kV (symmetric/asymmetric) acc. to EN 61000-4-5/IEC 61000-4-5

Line-fed disturbances

Criterion A; test voltage 10 V acc. to EN 61000-4-6/IEC 61000-4-6

Testing of disturbance transmission acc. to EN 61000-6-3

Radio disturbance characteristics

Class A acc. to EN 55022

Approvals

The current approvals can be found at www.boschrexroth.com.

technical illustration-R911173120-Cabinet I/O S20

Dimensions

Type

S20-AI6-AO2-SSI2

A

mm

53.6

B

mm

126.1

C

mm

54

Note on dimensions