BOSCH REXROTH
R-IBIL24SEG/F-PAC
R911170790
I/O Rexroth Inline PWR modules
BOSCH REXROTH
MATERIAL: R911170790
SUMMARY: I/O Rexroth Inline PWR modules
Quantity in stock: 1
Quantity Details:- Hydrotech Stock: 0 can ship May 7, 2024
- Factory Stock: 1 can ship June 25, 2024
This module is designed for use within an Inline station. It can be used to build a fuse-protected sub-circuit (segment circuit) within a main circuit. The module cannot be used to supply power, so it does not come with any reverse polarity or overvoltage protection.
General data
Type |
R-IB IL 24 SEG/F-PAC | |
Weight 1) |
g |
59 |
Ambient temperature (operation) |
-25 °C ... +55 °C | |
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
Permissible relative humidity (operation) |
10 % ... 95 %, EN 61131-2 | |
Permissible relative humidity (storage/transport) |
10 % ... 95 %, EN 61131-2 | |
Air pressure (operation) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20, IEC 60529 | |
Protection class |
III, EN 61113-2, IEC 61113-2 |
1) | Including plug |
Connection data
Type |
R-IB IL 24 SEG/F-PAC | |
Designation |
Inline connection plug | |
Connection type |
Tension spring modules | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
Interface local bus
Type |
R-IB IL 24 SEG/F-PAC | |
Transmission speed 1) |
kBit/s MBit/s |
500 2 |
1) | Can be used with this transmission speed in Inline stations, if required |
24 V peripheral supply |
The voltage is fed in the bus coupler or in the feed module. Connections for the supply voltage are not needed at the segment module. The corresponding module points are available only for test purposes. |
Permissible total current in the potential jumpers of the main and segment circuits
Type |
R-IB IL 24 SEG/F-PAC | |
Permissible total current in the potential jumpers |
A |
8 |
Nominal module current |
A |
6 |
Protective devices
Type |
R-IB IL 24 SEG/F-PAC | |
Overload/short-circuit protection in the segment circuit |
Safety fuse 5 x 20 mm with 6.3 A time-lag (maximum value of fuse 8 A. For fuses with a value of greater than 2 A, only use slow fuses!) | |
Reverse polarity protection |
Protection components in the feed module or in the bus coupler | |
Overvoltage protection |
Protection components in the feed module or in the bus coupler |
Electrical isolation/insulation of the voltage ranges
Type |
R-IB IL 24 SEG/F-PAC | |
Common potentials |
||
24 V main voltage UM, 24 V segment voltage US and GND are on the same potential. FE represents a separate potential area. |
||
Separate potentials in the system of bus coupler/feed module and I/O module |
||
Test distance |
Test voltage | |
5 V supply incoming remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
5 V supply to further remote bus/7.5 V supply (bus logic) |
500 V AC, 50 Hz, 1 min. | |
7.5 V supply (bus logic)/24 V supply (peripherals) |
500 V AC, 50 Hz, 1 min. | |
24 V supply (peripherals)/function earth |
500 V AC, 50 Hz, 1 min. |
Error messages to the higher-level control or computer system
Type |
R-IB IL 24 SEG/F-PAC | |
Error message |
None |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
R-IB IL 24 SEG/F-PAC | |
A |
mm |
12.2 |
B |
mm |
120 |
C |
mm |
71.5 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |