General data
Type |
R-IB IL 24/230 DOR 1/W-PAC | |
Weight 1) |
g |
61 |
Operating mode |
Process data operation with 2 bits | |
Actuator connection type |
Floating SPDT relay contact | |
Ambient temperature (operation) |
-25 °C ... +55 °C | |
Ambient temperature (storage/transport) |
-25 °C ... +85 °C | |
Permissible relative humidity (storage/transport) |
10 % ... 95 % acc. to DIN EN 61131-2 | |
Air pressure (operation) |
80 kPa ... 106 kPa (up to 2000 m above sea level) | |
Air pressure (storage/transport) |
70 kPa ... 106 kPa (up to 3000 m above sea level) | |
Protection type |
IP20, IEC 60529 |
1) | Including plug |
Connection data
Type |
R-IB IL 24/230 DOR 1/W-PAC | |
Designation |
Inline connection plug | |
Connection type |
Tension spring modules | |
Conductor cross-section solid/flexible/AWG |
0.2 mm² ... 1.5 mm² 0.2 mm² ... 1.5 mm² 24 ... 16 |
Interface local bus
Type |
R-IB IL 24/230 DOR 1/W-PAC | |
Connection type |
Data ranking | |
Transmission speed |
kBit/s |
500 |
Inline potentials/performance balance
Type |
R-IB IL 24/230 DOR 1/W-PAC | |
Logic voltage |
V DC |
7.5 |
Maximum current consumption from UL |
mA |
60 |
Maximum power consumption from UL |
W |
0.45 |
Supply of module electronics and peripherals via bus coupler/power feed module
Type |
R-IB IL 24/230 DOR 1/W-PAC | |
Connectivity technology |
Potential jumpers |
Relay output
Type |
R-IB IL 24/230 DOR 1/W-PAC | |||
Number of outputs |
1 | |||
Contact material |
AgSnO2, hard gold-plated | |||
Transfer resistance of the contact |
At 100 mA/6 V |
50 mΩ | ||
Limiting continous current |
At maximum ambient temperature |
3 A | ||
Maximum switching voltage |
253 V AC 250 V DC |
|||
Maximum switching power 1) |
AC/DC |
750 VA | ||
Minimum load |
5 V 10 mA |
|||
Switching current |
At 30 V DC |
3 A | ||
At 250 V DC |
0.15 A | |||
At 253 V DC |
3 A | |||
Maximum inrush current peak 2) |
For lamp loads and capacitive loads |
6 A | ||
Nominal current consumption of the coil (at 20 °C) |
From 7.5 V power supply |
210 mW | ||
Resistance of the coil (at 20 °C) |
±12 Ω |
119 Ω | ||
Maximum switching frequency |
No load |
Switching cycles/minute |
1200 GHz | |
At nominal load |
Switching cycles/minute |
6 GHz | ||
Typical response delay |
5 ms | |||
Typical bouncing time |
5 ms | |||
Typical release time |
6 ms | |||
Service life |
Mechanical |
Switching cycles |
2 x 107 | |
Electrical 3) |
Switching cycles |
105 | ||
Common potentials |
All contacts floating |
1) | See derating |
2) | For T = 200 μs |
3) | With 20 switching cycles/minute |
Power dissipation |
|
Formula for calculating the power dissipation in the module |
|
PEL = PBUS + (PREL) + PL |
|
PEL = 0.19 W + (0.26 W) + IL2x 0.05 Ω |
|
where: |
|
PEL |
Total power dissipation in the module |
PBUS |
Power dissipation due to the bus operation |
PREL |
Power dissipation in relay coil |
PL |
Power dissipation due to load current over the contacts |
IL |
Load current of output |
Power dissipation of housing dependent on the ambient temperature |
|
PGEH = 1.2 W |
-25 °C < TU ≤ +25 °C |
PGEH = 1.2 W ‒ ((TU ‒ 25 °C) x 0.02 W/°C) |
+25 °C < TU ≤ +55 °C |
where: |
|
PGEH |
Admissible power dissipation of housing |
TU |
Ambient temperature |
Derating when using the N/O contacts
Ambient temperature TU |
40 °C | 45 °C | 50 °C | 55 °C | |
Power dissipation in the housing |
W |
0.9 | 0.8 | 0.7 | 0.6 |
Maximum load current |
A |
3 | 2.6 | 2.2 | 1.7 |
Up to an ambient temperature of 40 °C, you can allow the maximum permissible load current of 3 A to flow via the N/O contacts. Be aware of derating at higher temperatures. |
Error messages to the higher-level control or computer system
Type |
R-IB IL 24/230 DOR 1/W-PAC | |
Error message |
None |
Air and creepage distances (acc. to EN 50178, VDE 0109, VDE 0110)
Partition section |
Relay contact/bus logic | Contact/contact | Contact/PE | |
Clearance |
mm |
≥ 5.5 | ≥ 3.1 | ≥ 3.1 |
Creepage distance |
mm |
≥ 5.5 | ≥ 3.1 | ≥ 3.1 |
Test voltage |
4 kV, 50 Hz, 1 min. | 1 kV, 50 Hz, 1 min. |
Approvals |
The current approvals can be found at www.boschrexroth.com. |
Dimensions
Type |
R-IB IL 24/230 DOR 1/W-PAC | |
A |
mm |
12.2 |
B |
mm |
120 |
C |
mm |
71.5 |
Note on dimensions |
The depth applies when using a support rail TH 35-7.5 (acc. to EN 60715). |